Vacuum circuit breaker V

Vacuum circuit breaker V

Vacuum circuit breaker cabinet V: breaking short circuit current of vacuum circuit breaker is provided with reclosure function. Between the isolation-ground-vacuum switch of load switch and three-position switch, mechanical interlocking is set and working position indication is displayed on the panel. Relay protection equipment provides overcurrent and quick-break and other protection functions.

BACK

Type report number 16Q0194-S 15Q0235-S 15Q1688-S
Model YCC-V-12(Z)/T630-20 YCC-V-24(Z)/T630-20 YCG-V-12(Z)/T1250-31.5
Rated voltage 12kV 24kV 12kV
Rated current 630A 630A 1250A
Rated frequency 50Hz 50Hz 50Hz
1min rated short-time power frequency withstand voltage (phase / fracture) 42/48kV 65/79kV 42/48kV
Rated lightning impulse withstand voltage (phase / fracture) 75/85kV 125/145kV 75/85kV
Basic short circuit test mode T10 2kA T10 2kA T10 3.15kA
T30 6kA T30 6kA T30 9.45kA
T60 12kA T60 12kA T60 18.9kA
T100s 20kA,50kA peak T100s 20kA,50kA peak T100s 31.5kA,80kA peak
T100a 20kA,DC:47% T100a 20kA,DC:45% T100a 31.5kA,DC:45%
Rated short circuit breaking current breaking times 20kA,30 times 20kA,30 times 31.5kA,30 times
Out of phase fault test 17.32kA 17.32kA 27.4kA
Single - phase cable charging current opening and closing test CC1 2.5A~10A,48 times“"O" CC1 2.5A~10A,48 times“"O" CC1 2.5A~10A,24 times“"O"
CC2 ≥25A,24 times“"O" CC2 ≥25A,24 times“"O" CC2 ≥25A,24 times“"CO"
CC2 ≥25A,24 tinmes“"CO" CC2 ≥25A,24 times“"CO" CC2
Three - phase capacitor group (single) current opening and closing test BC1 63A~252A,24 times"O" BC1 63A~252A,24 times "O" BC1 125A~500A,24 times"O"
BC2 ≥630A,80 times"CO" BC2 ≥630A,80 times"CO" BC2 ≥1250A,80 times"CO"
Three - phase capacitor group (back to back) current opening and closing test BC1 40A~160A,24 times"O" BC1 40A~160A,24 times"O" BC1 80A~320A,24 times"O"
BC2 ≥400A,80 times"CO" BC2 ≥400A,80 times"CO" BC2 ≥800A,80 times"CO"
Rated earthing switch short circuit closing current 50kA 50kA 80kA
Rated short-circuit withstand current (main circuit / ground circuit) 20kA 20kA 31.5kA
Rated short time withstand current duration 4s 4s 4s
Rated peak withstand current (main circuit / ground loop) 50kA 50kA 80kA
Partial discharge test 20pC 10pC 10pC
Arc test 20kA/0.5s 20kA/0.5s 20kA/0.5s
Annual leak rate 0.10% 0.10% 0.10%
Mechanical life 10000 times 10000 times 10000 times
Weight 215kg 215kg 220kg