型式报告编号 | 16Q0194-S | 15Q0235-S | 15Q1688-S | |||
型号 | YCC-V-12(Z)/T630-20 | YCC-V-24(Z)/T630-20 | YCG-V-12(Z)/T1250-31.5 | |||
额定电压 | 12kV | 24kV | 12kV | |||
额定电流 | 630A | 630A | 1250A | |||
额定频率 | 50Hz | 50Hz | 50Hz | |||
1min额定短时工频耐受电压(相间/断口) | 42/48kV | 65/79kV | 42/48kV | |||
额定雷电冲击耐受电压(相间/断口) | 75/85kV | 125/145kV | 75/85kV | |||
基本短路试验方式 | T10 | 2kA | T10 | 2kA | T10 | 3.15kA |
T30 | 6kA | T30 | 6kA | T30 | 9.45kA | |
T60 | 12kA | T60 | 12kA | T60 | 18.9kA | |
T100s | 20kA,50kA峰值 | T100s | 20kA,50kA峰值 | T100s | 31.5kA,80kA峰值 | |
T100a | 20kA,DC:47% | T100a | 20kA,DC:45% | T100a | 31.5kA,DC:45% | |
额定短路开断电流开断次数 | 20kA,30次 | 20kA,30次 | 31.5kA,30次 | |||
异相接地故障试验 | 17.32kA | 17.32kA | 27.4kA | |||
单相电缆充电电流开合试验 | CC1 | 2.5A~10A,48次“"O" | CC1 | 2.5A~10A,48次“"O" | CC1 | 2.5A~10A,24次“"O" |
CC2 | ≥25A,24次“"O" | CC2 | ≥25A,24次“"O" | CC2 | ≥25A,24次“"CO" | |
CC2 | ≥25A,24次“"CO" | CC2 | ≥25A,24次“"CO" | CC2 | ||
三相电容器组(单个)电流开合试验 | BC1 | 63A~252A,24次"O" | BC1 | 63A~252A,24次"O" | BC1 | 125A~500A,24次"O" |
BC2 | ≥630A,80次"CO" | BC2 | ≥630A,80次"CO" | BC2 | ≥1250A,80次"CO" | |
三相电容器组(背靠背)电流开合试验 | BC1 | 40A~160A,24次"O" | BC1 | 40A~160A,24次"O" | BC1 | 80A~320A,24次"O" |
BC2 | ≥400A,80次"CO" | BC2 | ≥400A,80次"CO" | BC2 | ≥800A,80次"CO" | |
额定接地开关短路关合电流 | 50kA | 50kA | 80kA | |||
额定短路耐受电流(主回路/接地回路) | 20kA | 20kA | 31.5kA | |||
额定短时耐受电流持续时间 | 4s | 4s | 4s | |||
额定峰值耐受电流(主回路/接地回路) | 50kA | 50kA | 80kA | |||
局部放电试验 | 20pC | 10pC | 10pC | |||
燃弧试验 | 20kA/0.5s | 20kA/0.5s | 20kA/0.5s | |||
年漏气率 | 0.001 | 0.001 | 0.001 | |||
机械寿命 | 10000次 | 10000次 | 10000次 | |||
重量 | 215kg | 215kg | 220kg |