Features: provided with three working positions including connected, isolated and grounded; meet the following requirements: GB3804 and GB1985; 3 position switchgear consists of load switch and fast grounding switch; the switch axle is connected with the mechanism axle through the movable fit of magnetic fluid in front of the gas box of the switch cabinet; in the breaking process of load current, there is a special airway to carry out “blowing arc extinction” for arc, to ensure safe and reliable breaking performance; the insulation partitions are used between phases to avoid the short circuit between phases; the switch is placed in a stable environment filled with SF6 gas, to meet the GB / T11022 standard maintenance-free requirements.
| Model | YCC-12(F)/T630-20 | YCC-24(F)/T630-20 |
| Type report number | 16K0078-S | 16K0079-S |
| Rated voltage | 12kV | 24KV |
| Rated current | 630A | 630A |
| Rated frequency | 50Hz | 50Hz |
| 1min rated short-time power frequency withstand voltage (phase / fracture) | 42/48kV | 65/79kV |
| Rated lightning impulse withstand voltage (phase / fracture) | 75/85kV | 125/145kV |
| Rated active load breaking current | 630A | 630A |
| Closed circuit breaking current of rated distribution line | 630A | 630A |
| Rated cable charging breaking current | 25A | 25A |
| Rated circuit charge breaking current | 1A | 1.5A |
| Rated short circuit closing current | 50KA | 50KA |
| Rated earthing switch short circuit closing current | 50KA | 50KA |
| Rated earth fault breaking current | 31.5A | 31.5A |
| Rated Charging Breaking Current under Rated Earth Fault | 43.3A | 43.3A |
| Rated current under fault conditions | 1.73A | 2.60A |
| Rated short-circuit withstand current (main circuit / ground circuit) | 20KA | 20KA |
| Rated short time withstand current duration | 4s | 4s |
| Rated peak withstand current | 50KA | 50KA |