Features of the boundary protection controller: voltage acquisition; current acquisition; have interphase protection, zero sequence protection, telecommand and extended remote-control closing-opening function; fault detection: have short circuit, ground alarm and other detection and active upload function; record for storage fault of events: the current and voltage setting value shall be recorded not less than 20 times at the time of fault; support serial communication and adopt the standard balanced 101 communication protocol; configure a communication module and an external GPRS module when communicating with the master station separately; have power status indication, switch position status, switch energy storage status, phase overcurrent, ground indication, device anomalies, communication indications and other functions; support local constantan value setting, manual closing-opening operation and fault memory; the protective constant value can be set without charge; have local, remote and latch-up protection output switch; electrical interface with military-grade aviation connector or terminal; built-in super capacitor.
Operating Voltage | DC48V |
Working frequency | 50Hz |
The operating voltage allows the fluctuation range | ±20% |
Power consumption | <10W |
Sampling voltage input range (quadratic) | 0~300V |
Overcurrent protection current setting range (secondary) | 0~5A |
Zero sequence protection current setting range (secondary) | 0~3A |
Overcurrent protection action delay time | 0~0.5s |
Zero sequence protection action delay time | 0~60s |
Contact output life | ≥50000 times |
Power frequency withstand voltage | 2.5kV/1min |
Impact pressure | 5Kv |
Electrostatic discharge interference capability | IV |
Fast transient interference capability | IV |