For load switch-fuse combination, it is the load switch that bears the overload current and the closing & breaking of normal working current and also bears the closing & breaking of "transfer current". While the high-voltage fuse bears the short circuit protection of transformer high-voltage side and overload protection. For a set of load switch and the fuse with three triggers, once any trigger acts, its link gear will separate the brake of the three-phase load switch at the same time. The organic combination of both can help to meet the operating protection requirements of power distribution system under various normal and fault conditions.
Model | YCC-T-12/T125-31.5 | YCC-T-24/T125-31.5 |
Type report number | 15Q1691-S | 15Q1690-S |
Rated voltage | 12kV | 24kV |
Rated current | 125A | 125A |
Rated frequency | 50Hz | 50Hz |
1min rated short-time power frequency withstand voltage (phase / fracture) | 42/48kV | 65/79kV |
Rated lightning impulse withstand voltage (phase / fracture) | 75/85kV | 125/145kV |
Rated circuit charge breaking current | 31.5kA | 31.5kA |
Rated short circuit closing current | 80kA | 80kA |
Rated transfer current | 1750A | 1450A |
Rated commutation current | 1750A | 1450A |
Partial discharge test | 20pC | 20pC |
Arc test | 20kA/0.5s | 20kA/0.5s |
Annual leak rate | ≤0.1% | ≤0.1% |
Mechanical life | ≥5000 times | ≥5000 times |
Weight | 1400:178kg/1600:188kg | 1400:178kg/1600:188kg |